SPECIFICATIONS |
|
Measuring Ranges |
Earth Resistance : 0-20 Ohm/0-200 Ohm/0-2000 Ohm |
|
Earth Voltage : 0-200V AC (40-500Hz) |
Accuracy |
Earth Resistance : +/- (2%rdg+2dgt) or +/- 0.1 Ohm, which is greater |
|
Earth Voltage : +/- (1%rdg+2dgt) |
Earth Resistance Resolution |
0-20 Ohm (0.01 Ohm) |
|
0-200 Ohm (0.1 Ohm) |
td>
| 0-2000 Ohm (1 Ohm) |
Measuring System |
Earth Resistance by constant current inverter 820 Hz approx. 2mA |
Display |
LCD 3-1/2 digit (2000 counts) |
Open Circuit Indication |
LED will be unlit |
Low Battery Indication |
symbol appears on thedisplay |
Data Hold Indication |
symbol appears on the display |
Over Range Idication |
"1" (MSD) |
Power Source |
1.5V SUM-3 (AA) x 8 or equivalent |
Dimensions |
175(L) x 85(W) x 75(D) mm |
Weight |
Approx. 600g (battery included) |
Accessories |
Test leads (AL-36 : red-15m, yellow-10m, green-5m) |
|
Auxiliary earth spikes |
|
Simplified measurement probe |
|
Shoulder belt, instruction manual, batteries |