TYPE |
Load tap changer analyzer |
PHYSICAL SPECIFICATIONS |
25”W x 8.5”H x 20”D (63.5 cm x 21.6 cm x 50 cm); Weight: 46 lbs (20 kg) |
OPERATING VOLTAGE |
100 – 240 Vac, 50/60 Hz |
RESISTANCE READING RANGE |
1 micro-ohm – 500 ohms |
ACCURACY |
1 – 19,999 micro-ohms: ±0.5% reading, ±1 count;
20 – 999 milli-ohms: ±1% reading, ±1 count;
1 – 500 ohms: ±1.5% reading, ±1 count |
RESISTANCE CHANNELS |
Three static resistance reading channels, One dynamic resistance channel |
TEST VOLTAGE |
60 Vdc max |
TEST CURRENTS |
1 ampere, 5 amperes, 10 amperes, 40 amperes |
AC CURRENT INPUT |
Clamp-on current sensor, 1 – 20 amperes |
DISPLAY |
Back-lit LCD Screen (64 x 128 dot graphic ); viewable in bright sunlight and low-light levels |
PRINTER |
4.5-inch wide thermal printer |
EXTERNAL DATA STORAGE |
One USB Flash drive interface port; stores up to 999 test records on a USB Flash drive (not included) |
COMPUTER INTERFACES |
One RS-232C port, One USB port |
INTERNAL TEST RECORD STORAGE |
Stores up to 128 static resistance test records (48 tests per record) and 11 dynamic resistance test records |
LOAD TAP CHANGER CONTACT |
240 Vac, 1A |
SAFETY |
|
ENVIRONMENT |
Operating: -10C to 50 C (15F to +122 F); Storage: -30 C to 70 C (-22F to +158 F) |
CABLES |
One 50-foot current cable set, Three 50-foot resistance cable sets, One ground cable, One USB cable, One RS-232C cable, One LTC cable, power cord, cable bag |
OPTIONS |
Transportation Case |
WARRANTY |
One year on parts and labor |
Specifications are valid at nominal voltage and ambient temperature of +25C (+77F).
Last updated on February 13, 2009 |