TYPE |
10 – 600 Amp current source |
PHYSICAL SPECIFICATIONS |
16.8”W x 12.6”H x 10.6” D (42.6 cm by 32.0 cm by 27 cm); Weight: 46lbs (21kg) |
INPUT POWER |
100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50/60 Hz |
INTERNAL CURRENT METER |
100 mA – 1000 A; Accuracy: 1% of reading, ±20 mA |
MEASURING METHOD |
Isolated CT |
EXTERNAL METER RANGE |
10 mA – 10 A; Accuracy: 1% of reading, ±2 mA |
MEASURING METHOD |
Isolated CT |
TIMER READING RANGE |
1 ms – 2 hours; Accuracy: 0.1% of reading ±1ms |
TIMER STOP INPUT |
Voltage input (24 – 300 V, DC or peak AC), dry-contact input, or removal of primary current |
COMPUTER INTERFACE |
RS-232C port (19,200 baud) for factory calibration and diagnostics |
SAFETY |
|
ENVIRONMENT |
Operating: -10C to 50 C (15F to +122 F); Storage: -30 C to 70 C (-22F to +158 F) |
CABLES |
10-foot #1/0 AWG test leads, power cord, ground cable |
OPTIONS |
Transportation case |
WARRANTY |
One year on parts and labor |
Specifications are valid at nominal voltage and ambient temperature of +25C (+77F).
Last updated on February 13, 2009 |